Applying insights gained from industrial customers, rental companies, public utilities and other end users QAS generators are designed to withstand the most demanding on-site conditions and environments.
Considering their impressive performance at full capacity, the QAS line of generators includes excellent features for noise reduction and environmental protection.
QAS generators are purpose built for quick, easy and safe transport and on-site handling. Built to last, a QAS generator will provide years of dependable service for your electrical power generation needs. All members of the widely appreciated QAS family are intelligent multi-task units managing to power a wide range of electrical equipment in different applications.
Their superior component configuration offers a wide range of control modules, electrical settings and mechanical options, in order to guarantee superior quality at efficient operating costs.
Conceived for 100% prime power operation in the most severe outdoor conditions, ready to work in sensitive areas, QAS generators are designed and configured for safe operation with minimal downtime under any circumstance.
Key Features
- Carefully selected components, accurately developed and tested configuration
- Superior standard configuration and extensive option list
- 500 hours service interval and superior accessibility to all service points
- Compact and safe concept and sturdy design
- Designed and built to last
- Accurate and stable power regardless of the conditions
- Ability to power a wide range of applications
- Service efficiency: increased up-time
- Increased transport efficiency, separated control and power cubicle
- Superior resale value / longer life time
PERFORMANCE DATA
Generator | QAC1100 TW (50Hz) | QAC 1100 TW (60Hz) | ||
---|---|---|---|---|
Rated Speed | rpm | 1500 | 1800 | |
Rated Power Factor (lagging) | 0.8 | 0.8 | ||
Rated Prime Power, PRP | kVA | 1364 | 1450 | |
Rated Prime Power, PRP | kW | 1091 | 1160 | |
Limited Time Power, ESP (Standby) | kVA | 1446 | 1587 | |
Limited Time Power, ESP (Standby) | kW | 1157 | 1270 | |
Continuous Operation Power, COP | ||||
(Continuous)" | kVA | 1029 | 1091 | |
Continuous Operation Power, COP | ||||
(Continuous)" | kW | 823 | 873 | |
Rated voltage (3ph. line to line) | V | 400 | 480 | |
Rated voltage (1ph. line to neutral) | V | 230 | 277 | |
Rated voltage 3ph (PRP) | A | 1970 | 1744 | |
Rated voltage 3ph (ESP) | A | 2089 | 1909 | |
Rated voltage 3ph (COP) | A | 1485 | 1312 | |
Maximum sound power level (LWA) complies with 2000/14/EC | dB(A) | 103 | 106 | |
Maximum sound pressure level (LPA) at 7 m | dB(A) | 73 | 76 | |
Coupling engine/alternator | Disc Coupling | Disc Coupling | ||
Fuel Autonomy at full load | h | 7:30 | 7 | |
Single step load acceptance (within G2, acc. ISO 8528-5:1993) | % | 50 | 60 | |
Single step load capability | % | 100 | 100 | |
Frequency drop (lower than % isochronous) | % | <0.25 | <0.25 | |
Maxim oil consumption 100% load | L/H | 0.2 | 0.2 |